Fig 1 — A forward wave V⁺ reaches a load Z_L ≠ Z₀. Part of it is absorbed and part returns as V⁻ = Γ·V⁺.
Source line, Z₀ = 50 Ω Z_L forward wave V⁺ reflected wave V⁻ = Γ V⁺

Load Impedance and Reflections

In Part 2 we saw that a wave travelling along a line has V/I = Z₀. The line ends at a load — an antenna, an amplifier input, a filter — with impedance Z_L. The load forces its own ratio V/I = Z_L at the end of the line. If Z_L = Z₀ the forward wave alone satisfies that condition and all of its power is absorbed. If Z_L ≠ Z₀, the only way to satisfy both the line and the load is for a second wave to travel back toward the source. That returning wave is the reflection.

Reflections waste power, can damage transmitters, create ripple in frequency response and cause the standing waves of Part 4. Quantifying them is the first step toward removing them.

Definition of the Reflection Coefficient

The reflection coefficient Γ (gamma) is the ratio of the reflected voltage wave to the incident voltage wave at the load. Applying V = V⁺ + V⁻ and I = (V⁺ − V⁻)/Z₀ at the load and setting V/I = Z_L gives:

Reflection coefficient at the load
ΓL=V−V+=ZL−Z0ZL+Z0=z−1z+1 z=ZLZ0
The last form uses the normalised impedance z (Part 7). Γ depends only on the ratio Z_L/Z₀, which is why one Smith chart works for every Z₀. On a network analyser, Γ measured at port 1 is called S11.

The inverse relation lets us recover the load from a measured Γ:

Load impedance from Γ
ZL=Z01+ΓL1−ΓL

Magnitude and Phase of Γ

Because Z_L is generally complex, Γ is a complex number, usually written in polar form Γ = |Γ| ∠ θ.

  • Magnitude |Γ| (0 to 1 for passive loads) tells how much of the incident voltage comes back. |Γ|² is the fraction of incident power reflected.
  • Phase θ tells where the reflection sits in time relative to the incident wave. Positive θ means the load is inductive (above the real axis); negative θ means capacitive. θ = 0° and 180° correspond to purely resistive loads above and below Z₀.

Plotting Γ as a point in the complex plane — real part horizontal, imaginary part vertical — puts every passive load inside the unit circle |Γ| ≤ 1. That disc, with impedance circles drawn on it, is the Smith chart of Part 6.

Fig 2 — The Γ plane. Every passive load lies inside the unit circle; short, open and matched loads sit at three special points.
Short (z = 0)Open (z = ∞)Matched (z = 1)100 Ω25 + j50 Ω30 − j40 Ω
|Γ| = 1/3|Γ| = 0.62

Short, Open and Matched Loads

LoadZ_LΓWhat happensSmith chart position
MatchedZ₀0All power absorbed, no reflectionCentre
Short circuit0−1 = 1 ∠ 180°Total reflection, voltage inverted (V = 0 at load)Left edge
Open circuit∞+1 = 1 ∠ 0°Total reflection, current inverted (I = 0 at load)Right edge
Pure reactancejX|Γ| = 1Total reflection with a phase shiftOn the outer circle
💡 Why a reactance reflects everything

An ideal inductor or capacitor cannot absorb power — it only stores energy and gives it back. So whatever the value of X, |Γ| = 1 and the reflected wave carries all the power back. Only the phase depends on X.

Return Loss, S11 and Reflected Power

Engineers usually express the reflection in decibels. Return loss is how far below the incident power the reflected power is; S11 in dB is the same number with a minus sign:

Return loss, reflected and delivered power
RL=−20log10|Γ| dB PreflPinc=|Γ|2 PloadPinc=1−|Γ|2
A larger return loss is better. The common design target RL ≥ 10 dB (S11 ≤ −10 dB) means |Γ| ≤ 0.316: under 10% of the power is reflected and over 90% reaches the load.
|Γ|Return lossPower reflectedPower deliveredMismatch loss
0.03230 dB0.1%99.9%0.004 dB
0.120 dB1%99%0.04 dB
0.214.0 dB4%96%0.18 dB
0.31610 dB10%90%0.46 dB
0.56.0 dB25%75%1.25 dB
10 dB100%0%∞

Reading Γ in the Smith Chart Calculator

The Smith Chart Calculator computes Γ, S11 and VSWR for any load as you type it. Two loads that are equally mismatched in magnitude but opposite in phase illustrate the geometry well: 100 Ω and 25 Ω on a 50 Ω line both have |Γ| = 1/3, but one is to the right of centre and the other to the left.

Smith chart with a 100 ohm load on the horizontal axis to the right of centre
100 Ω: Γ = +0.333 ∠ 0°, to the right of centre on the r = 2 circle. Try it in the Smith Chart Calculator →
Smith chart with a 25 ohm load on the horizontal axis to the left of centre
25 Ω: Γ = 0.333 ∠ 180°, the mirror-image point on the r = 0.5 circle. Try it in the Smith Chart Calculator →
Calculator readouts for a 25 ohm load: Gamma 0.333 at 180 degrees, S11 minus 9.54 dB, VSWR 2.00
Calculator readout for 25 Ω: Γ = 0.333 ∠ 180°, S11 = −9.54 dB, VSWR 2.00 — the same magnitude as 100 Ω, only the phase differs. Try it in the Smith Chart Calculator →

Worked Examples

01

Resistive Loads Above and Below Z₀

Problem: Find Γ for 100 Ω and 25 Ω loads on a 50 Ω line, and the return loss of each.

Γ100=100−50100+50=+0.333 Γ25=25−5025+50=−0.333
Answer: Γ = 0.333 ∠ 0° and 0.333 ∠ 180°; both RL = 9.54 dB

A load twice Z₀ and a load half Z₀ are equally bad. Mismatch is about the ratio, not the difference.

02

A Complex Load: 30 − j40 Ω

Problem: Find Γ, the return loss and the reflected power fraction for Z_L = 30 − j40 Ω on a 50 Ω line.

Γ=−20−j4080−j40=−j0.5=0.5∠−90°
Smith chart with the load 30 minus j40 ohms plotted halfway down the vertical axis in the capacitive half
z = 0.6 − j0.8 lands exactly on the vertical axis, halfway to the bottom edge. Try it in the Smith Chart Calculator →
Calculator readouts for 30 minus j40 ohms: Gamma 0.500 at minus 90 degrees, S11 minus 6.02 dB, VSWR 3.00, mismatch loss 1.25 dB
Calculator readout: Γ = 0.500 ∠ −90°, S11 = −6.02 dB, VSWR 3.00, mismatch loss 1.25 dB. Try it in the Smith Chart Calculator →
Answer: Γ = 0.5 ∠ −90°, RL = 6.02 dB, 25% of the power reflected

The negative angle confirms the capacitive load. Only 75% of the incident power reaches it.

03

Inductive Load: 25 + j50 Ω

Problem: A small antenna measures 25 + j50 Ω on a 50 Ω line. What fraction of the power is reflected?

Γ=−25+j5075+j50=0.620∠82.9° |Γ|2=31258125=0.385
Answer: |Γ| = 0.620, 38.5% of the power reflected (RL = 4.15 dB)

This load is the running example of the series; Part 10 matches it to 50 Ω with two components.

04

A Purely Reactive Load

Problem: Find Γ for Z_L = j50 Ω on a 50 Ω line.

Γ=j50−50j50+50=−1+j1+j=j=1∠90°
Answer: |Γ| = 1, θ = +90° — total reflection

The point sits at the top of the Smith chart, where the x = +1 arc meets the outer circle.

05

Recovering the Load From a Measurement

Problem: A network analyser measures S11 = 0.2 ∠ 0° on a 50 Ω port. What is the load?

ZL=50×1+0.21−0.2=75 Ω
Answer: Z_L = 75 Ω (RL = 14.0 dB, 4% reflected)

This is exactly a 75 Ω device on a 50 Ω system — a common, mild mismatch.

Summary

  • A load Z_L ≠ Z₀ reflects part of the incident wave; Γ = (Z_L − Z₀)/(Z_L + Z₀) = (z − 1)/(z + 1).
  • |Γ| ranges from 0 (matched) to 1 (short, open, or pure reactance); the phase shows whether the load is inductive or capacitive.
  • Return loss = −20 log|Γ|; reflected power fraction = |Γ|². The usual target is RL ≥ 10 dB.
  • Plotting Γ in the complex plane puts every passive load inside the unit circle — the basis of the Smith chart.

The forward and reflected waves interfere along the line. Part 4: Standing Waves and Voltage Standing Wave Ratio (VSWR) shows the standing-wave pattern they create and how VSWR measures it.

Put It Into Practice

Use the NEXT ANTENNAS calculators to apply the ideas from this article to real designs.